SI4080 is a digital measuring, fully programmable device from the 4080 series, designed on the basis of microcontrollers. SI4080 shows the current position of the tap changer of the high-voltage transformer in electrical substations.
The unit is part of tap changer-motor drive equipment. The position of the tap changer can be read either analogue (by resistor matrix) or digital (BIN or BCD input). The unit is designed to be mounted on boards in control rooms of electrical substations.
| input | analog / BIN / BCD |
| digital input voltage range | 5-48 VDC |
| analogue input single resistor step | 6/8/10 Ohm |
| analogue input maximum matrix resistance | 390 Ohm |
| analogue input maximum steps | 39 when 10 Ohm; 48 when 8 Ohm; 64 when 6 Ohm |
| digital input maximum steps | 127 when BIN-input; 79 when BCD-input |
| maximum wiring length | * 200 m / 0.75 mm²; 400m / 1.5 mm²; 700m / 2.5 mm² |
| power supply | 55-250 VAC (80-350 VDC) / 30-270 VAC (42-380 VDC) |
| display | super bright red, 4-digit, 76х25 mm visible, purple filter |
| power consumption | < 3 W |
| work temperature | from 0° C to 55° C |
| storage temperature | from -50° C to +90° C |
| dimensions (H/W/D) | 48/96/85 mm or 96/96/85 mm (w/o plugs); 48/96/95 mm or 96/96/95 mm (with plugs) |
| mounting hole (H/W) | 43/90 mm or 90/90 mm quad, centered |
| protection class | IP52 front, IP31 back |
| own weight | 320 g |
| For further information visit www.gineers.com/en |