Software Activation
ISMA IO Modules Mix Series

iSMA-B-MIX18

Multiprotocol I/O module with the most common MIX of 18 inputs and outputs in building automation.

Multiprotocol Module with a MIX of I/O’s – the Ultimate Controller Extension
Powerful I/O module that works as a remote I/O over a serial port with open protocols, BACnet MS/TP and Modbus RTU/ASCII. Open protocols standard offers the versatility of installing the modules in both new and existing facilities, whether it is a system expansion or a retrofit. The most popular types of inputs and outputs are MIXed in a space-saving design and allow the module to be a versatile controller extension, whether in a small or large facility.

5 Universal Inputs
Support for over 20 types of temperature sensors and voltage, resistance, current, and dry contact measurements on each universal input.

5 Digital Inputs
Dry contact inputs – made for monitoring. 100 Hz fast pulse counter with override function saves the real-time values to the EEPROM memory.

4 Digital Outputs
Digital outputs equipped with normally open 3 A relays allow for a direct control without additional relays.

4 Analog Outputs
0-10 V DC control with 10 mA accuracy, PWM modes, and a maximum load of up to 20 mA to power external relays makes the output suitable for a variety of scenarios.

Simplified Configuration and Commissioning Process
The module allows for seamless configuration over BACnet, Modbus or dedicated free of charge tool. The ability to be powered from a USB port facilitates local testing and a straightforward updating process, and the high-end RS485 transceiver allows up to 128 devices to communicate reliably with the client on a single bus.

Quality and Reliability Confirmed by Certificates
iSMA CONTROLLI is a long-standing member of the BACnet community. The experience in developing high quality products and the BTL (BACnet Test Laboratory) certification confirm the excellent performance of communication using the BACnet protocol.
Reliability of operation is confirmed by UL testing, certified by Underwriters Laboratories.

Technical Specification

Hardware Specification
RS485 interface
mini USB type B interface
Status LED indicators
DIN rail mounted
18 I/Os onboard

Inputs
5 Universal Inputs (UI)
Temperature input in Celcius degrees: 10K3A1, 10K4A1, Carel 10K, 20K6A1, 2.2K3A1, 3K3A1, 30K6A1, SIE1, TAC1, SAT1, Pt1000, Ni1000 0C, Ni 1000 20C, Ni1000 LG 2
Temperature input in Fahrenheit degrees: 10K Type2, 10K type3, 20K, 3K, PT 1000, Ni 1000 32F, Ni 1000 70F
Resistive input 0-1000 kΩ
Voltage input 0-10 V DC
Current input 0-20 mA
Dry contact input

5 Digital Inputs (DI)
Dry contact inputs
Fast pulse counter up to 100 Hz saved in the EEPROM memory

Outputs
4 Digital Outputs (DO)
NO relay output
Resistive load max. 3 A @ 230 V AC / 30 V DC
Inductive load max. 75 VA @ 230 V AC / 30 W @ 30 V DC

4 Analog Outputs (AO)
Output 0-10 V DC maximum load up to 20 mA
PWM: 0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz, 100 Hz

Communication
BACnet MS/TP
Modbus RTU/ASCII
Free software iSMA Configurator
Dedicated Niagara Framework modules

Power Supply
24 V DC ± 20%
24 V AC ± 20%

ISMA-B-MIX18

iSMA-B-MIX18-IP

Multiprotocol I/O module with the most common MIX of 18 inputs and outputs in building automation. Equipped with IP connectivity, and built-in Modbus TCP/IP to Modbus RTU/ASCII Gateway.

Multiprotocol Module with a MIX of I/O’s – the Ultimate Controller Extension
Powerful I/O module that works as a remote or distributed I/O over IP with open protocols, BACnet IP and Modbus TCP/IP. Open protocol standard offers the versatility of installing the modules in both new and existing facilities, whether it is a system expansion or a retrofit. The most popular types of inputs and outputs are MIXed in a space-saving design and allow the module to be a versatile controller extension, whether in a small or large facility.

5 Universal Inputs
Support for over 20 types of temperature sensors and voltage, resistance, current, and dry contact measurements on each universal input.

5 Digital Inputs
Dry contact inputs – made for monitoring. 100 Hz fast pulse counter with override function saves the real-time values to EEPROM memory.

4 Digital Outputs
Digital outputs equipped with normally open 3 A relays allow for direct control without additional relays.

4 Analog Outputs
0-10 V DC control with 10 mA accuracy, PWM modes, and a maximum load of up to 20 mA to power external relays makes the output suitable for a variety of scenarios.

Modbus TCP/IP to Modbus RTU/ASCII Gateway
Built-in Modbus gateway on the COM1 port enables integration of up to 128 Modbus slave devices to the IP layer.

Simplified Configuration and Commissioning Process
The module allows for seamless configuration over BACnet, Modbus, built-in web server, or dedicated free of charge tool. The ability to be powered from a USB port facilitates local testing and enables a straightforward updating process. Two Ethernet ports working in a switch-mode allow for daisy chaining multiple modules over the RJ45, which improves the cabling process and reduces engineering time.

Quality and Reliability Confirmed by Certificates
iSMA CONTROLLI is a long-standing member of the BACnet community. The experience in developing high quality products and the BTL (BACnet Test Laboratory) certification confirm the excellent performance of communication using the BACnet protocol.
Reliability of operation is confirmed by UL testing, certified by Underwriters Laboratories.

Technical Specification

Hardware Specification
2 Ethernet ports with built-in switch
RS485 interface
mini USB type B interface
Status LED indicators
DIN rail mounted
18 I/Os onboard

Inputs
5 Universal Inputs (UI)
Temperature input in Celcius degrees: 10K3A1, 10K4A1, Carel 10K, 20K6A1, 2.2K3A1, 3K3A1, 30K6A1, SIE1, TAC1, SAT1, Pt1000, Ni1000 0C, Ni 1000 20C, Ni1000 LG 2
Temperature input in Fahrenheit degrees: 10K Type2, 10K type3, 20K, 3K, PT 1000, Ni 1000 32F, Ni 1000 70F
Resistive input 0-1000 kΩ
Voltage input 0-10 V DC
Current input 0-20 mA
Dry contact input

5 Digital Inputs (DI)
Dry contact inputs
Fast pulse counter up to 100 Hz saved in EEPROM memory

Outputs
4 Digital Outputs (DO)
NO relay output
Resistive load max. 3 A @ 230 V AC / 30 V DC
Inductive load max. 75 VA @ 230 V AC / 30 W @ 30 V DC

4 Analog Outputs (AO)
Output 0-10 V DC maximum load up to 20 mA
PWM: 0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz, 100 Hz

Communication
BACnet IP
Modbus TCP/IP
Modbus TCP/IP to Modbus RTU/ASCII Gateway
Free software iSMA Configurator
Built-in web server
Dedicated Niagara Framework modules

Power Supply
24 V DC ± 20%
24 V AC ± 20%

ISMA-B-MIX18-IP

ISMA-B-Mix-38

Multiprotocol I/O module with the most common MIX of 38 inputs and outputs in building automation.

Multiprotocol Module with a MIX of I/O’s – the Ultimate Controller Extension
The most versatile I/O module with 38 inputs and outputs, offering the most cost-effective price per point ratio. Powerful I/O module that works as a remote I/O over a serial port with open protocols: BACnet MS/TP, and Modbus RTU/ASCII. Open protocols standard offers the versatility of installing the modules in both new and existing facilities, whether it is a system expansion or a retrofit. The most popular types of inputs and outputs are MIXed in a space-saving design and allow the module to be a versatile controller extension, whether in a small or large facility.

8 Universal Inputs
Support for over 20 types of temperature sensors and voltage, resistance, current, and dry contact measurements on each universal input.

12 Digital Inputs
Dry contact inputs – made for monitoring. 100 Hz fast pulse counter with override function saves the real-time values to the EEPROM memory.

12 Digital Outputs
Digital outputs equipped with normally open 3 A relays allow for a direct control without additional relays.

6 Analog Outputs
0-10 V DC control with 10 mA accuracy, PWM modes, and a maximum load of up to 20 mA to power external relays makes the output suitable for a variety of scenarios.

Simplified Configuration and Commissioning Process
The module allows for seamless configuration over BACnet, Modbus or dedicated free of charge tool. The ability to be powered from a USB port facilitates local testing and a straightforward updating process, and the high-end RS485 transceiver allows up to 128 devices to communicate reliably with the client on a single bus.

Quality and Reliability Confirmed by Certificates
iSMA CONTROLLI is a long-standing member of the BACnet community. The experience in developing high quality products and the BTL (BACnet Test Laboratory) certification confirm the excellent performance of communication using the BACnet protocol.
Reliability of operation is confirmed by UL testing, certified by Underwriters Laboratories.

Technical Specification

Hardware Specification
RS485 interface
mini USB type B interface
Status LED indicators
DIN rail mounted
38 I/Os onboard

Inputs
8 Universal Inputs (UI)
Temperature input in Celcius degrees: 10K3A1, 10K4A1, Carel 10K, 20K6A1, 2.2K3A1, 3K3A1, 30K6A1, SIE1, TAC1, SAT1, Pt1000, Ni1000 0C, Ni 1000 20C, Ni1000 LG 2
Temperature input in Fahrenheit degrees: 10K Type2, 10K type3, 20K, 3K, PT 1000, Ni 1000 32F, Ni 1000 70F
Resistive input 0-1000 kΩ
Voltage input 0-10 V DC
Current input 0-20 mA
Dry contact input

12 Digital Inputs (DI)
Dry contact inputs
Fast pulse counter up to 100 Hz saved in the EEPROM memory

Outputs
12 Digital Outputs (DO)
NO relay output
Resistive load max. 3 A @ 230 V AC / 30 V DC
Inductive load max. 75 VA @ 230 V AC / 30 W @ 30 V DC

6 Analog Outputs (AO)
Output 0-10 V DC with a maximum load up to 20 mA
PWM: 0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz, 100 Hz

Communication
BACnet MS/TP
Modbus RTU/ASCII
Free software iSMA Configurator
Dedicated Niagara Framework modules

Power Supply
24 V DC ± 20%
24 V AC ± 20%

ISMA-B-MIX38

iSMA-B-MIX38-IP

Multiprotocol I/O module with the most common MIX of 38 inputs and outputs in building automation. Equipped with IP connectivity, and built-in Modbus TCP/IP to Modbus RTU/ASCII Gateway.

Multiprotocol Module with a MIX of I/O’s – the Ultimate Controller Extension
The most versatile I/O module with 38 inputs and outputs, offering the most cost-effective price per point ratio. Powerful I/O module that works as a remote or distributed I/O over IP with open protocols: BACnet IP, and Modbus TCP/IP. Open protocols standard offers the versatility of installing the modules in both new and existing facilities, whether it is a system expansion or a retrofit. The most popular types of inputs and outputs are MIXed in a space-saving design and allow the module to be a versatile controller extension, whether in a small or large facility.

8 Universal Inputs
Support for over 20 types of temperature sensors and voltage, resistance, current, and dry contact measurements on each universal input.

12 Digital Inputs
Dry contact inputs – made for monitoring. 100 Hz fast pulse counter with override function saves the real-time values to the EEPROM memory.

12 Digital Outputs
Digital outputs equipped with normally open 3 A relays allow for direct control without additional relays.

6 Analog Outputs
0-10 V DC control with 10 mA accuracy, PWM modes, and a maximum load of up to 20 mA to power external relays makes the output suitable for a variety of scenarios.

Modbus TCP/IP to Modbus RTU/ASCII Gateway
Built-in Modbus gateway on the COM1 port enables integration of up to 128 Modbus slave devices to the IP layer.

Simplified Configuration and Commissioning Process
The module allows for seamless configuration over BACnet, Modbus, built-in web server, or dedicated free of charge tool. The ability to be powered from a USB port facilitates local testing and a straightforward updating process. Two Ethernet ports working in a switch mode allow for daisy chaining of multiple modules over the RJ45, which facilitates the cabling process and reduces engineering time.

Quality and Reliability Confirmed by Certificates
iSMA CONTROLLI is a long-standing member of the BACnet community. The experience in developing high quality products and the BTL (BACnet Test Laboratory) certification confirm the excellent performance of communication using the BACnet protocol.
Reliability of operation is confirmed by UL testing, certified by Underwriters Laboratories.

Technical Specification

Hardware Specification
2 Ethernet interface with built-in switch
RS485 interface
mini USB type B interface
Status LED indicators
DIN rail mounted
38 I/Os onboard

Inputs
8 Universal Inputs (UI)
Temperature input in Celcius degrees: 10K3A1, 10K4A1, Carel 10K, 20K6A1, 2.2K3A1, 3K3A1, 30K6A1, SIE1, TAC1, SAT1, Pt1000, Ni1000 0C, Ni 1000 20C, Ni1000 LG 2
Temperature input in Fahrenheit degrees: 10K Type2, 10K type3, 20K, 3K, PT 1000, Ni 1000 32F, Ni 1000 70F
Resistive input 0-1000 kΩ
Voltage input 0-10 V DC
Current input 0-20 mA
Dry contact input

12 Digital Inputs (DI)
Dry contact inputs
Fast pulse counter up to 100 Hz save in EEPROM memory

Outputs
12 Digital Outputs (DO)
NO relay output
Resistive load max. 3 A @ 230 V AC / 30 V DC
Inductive load max. 75 VA @ 230 V AC / 30 W @ 30 V DC

6 Analog Outputs (AO)
Output 0-10 V DC maximum load up to 20 mA
PWM: 0.01 Hz, 0.1 Hz, 1 Hz, 10 Hz, 100 Hz

Communication
BACnet IP
Modbus TCP/IP
Modbus TCP/IP to Modbus RTU/ASCII Gateway
Free software iSMA Configurator
Built-in web server
Dedicated Niagara Framework modules

Power Supply
24 V DC ± 20%
24 V AC ± 20%

ISMA-B-MIX38-IP

Related Products

Ready to Ship

Ready to Ship

Metering products and reading system modules are ready to ship

Next Day Delivery

Next Day Delivery

Order before 5pm for guaranteed next day delivery on stocked products

Free Help & Support

Free Help & Support

Free lifetime technical support on all products and systems by B METERS

Quality Guaranteed

Quality Guaranteed

We've been manufacturing precise measurement instruments for over 25 years

Make an enquiry





    Copyright © 2024 B Meters UK LTD  |  Privacy Policy